Design Parameters (Comfort cooling)
Indoor: 22°Cdb / 50% RH
Outdoor: 28°Cdb / 50%RH
Occupancy:
10 sqM per Person
Heat output per Person:
90w Sensible
50w Latent
Total = 140w/person
Heat output per sqM :
9w/sqM
5w/sqM
Total = 14w/sqM
Ventilation
12 l/sec/person (typical office)
Heat input per Person:
90w Sensible
130w Latent
Total = 220w/person
Per sqM:
9w/sqM
13w/sqM
Total = 22w/sqM
Infiltration:
0.25 Air change per hour
Heat input per sqM:
1.3w Sensible
2w Latent
Total = 3.3w/sqM
Lighting:
20 - 25 w/sqM
Small Power:
20 - 40 w/sqM
Construction Heat gain:
Windows/ Double Glazed
2.8w/sqM°C
= 16.8w/sqM at 6°C DT
Walls - External
0.45 w/sqM°C
= 2.7w/sqM at 6°C DT
Roof
0.35 w/sqM°C
= 2.1w/sqM at 6°C DT